- 120V
- 60 Hz
- 0.9 Amps
- 70 Watts Running
- 25 Watts Holding
- 108 VA Running
- 42 VA Holding
- 60 (6.8) Rated Torque lb-in (N-m)
- 20 No Load Timing in Seconds at 75 F
- Mounting Output Shaft Must be Horizontal
- Shaft Rotation CW 170 Degrees when power is applied
- Operating Temperature -40 to 136 F
Features
- Rugged die cast aluminum with two 1/2” conduit openings
- Oil immersed motor and gear train
- Spring Return
For two-position operation of dampers, valves, and other equipment which require the return to normal position upon power interruption.