π₯ EP160 FIREYE PROGRAMMER MODULE β NON-RECYCLE
π Product Overview
The Fireye EP160 Programmer Module is a non-recycle control module designed for use with E100 and E110 Flame-Monitor systems. It provides precise burner startup programming, safe-start checks, and continuous flame supervision to ensure reliable and safe burner operation.
Featuring a 30-second purge, 10-second PTFI/MTFI ignition timing, and 4-second flame failure response time, the EP160 delivers dependable safety control for a wide range of industrial and commercial combustion systems.
π© Exact Replacement For:
Power Flame 398100
β
Key Features
π Non-Recycle Operation β Designed to lockout on flame failure for maximum system safety.
π Fast Flame Failure Response β De-energizes all fuel valves within 4 seconds of flame loss.
π Built-In Purge Cycle β 30-second high-fire purge ensures a clean, safe light-off.
π Reliable Ignition Timing β Features 10-second Pilot Trial-for-Ignition (PTFI) and Main Trial-for-Ignition (MTFI).
π Comprehensive Safety Supervision β Monitors interlocks, airflow, and fuel pressure for consistent reliability.
π Memory Retention β Stores burner cycles, hours, and lockout history for maintenance tracking.
π Service-Friendly Design β Includes a Check-Run switch for easy system setup and troubleshooting.
π Plug-and-Play Integration β Compatible with Fireye E100/E110 Flame-Monitor systems.
π Communication-Ready β Equipped with RJ45 (for ED510 display) and RJ12 Modbus connectors.
βοΈ Technical Specifications
| Specification | Details |
| Manufacturer |
Fireye |
| Model |
EP160 |
| Type |
Programmer Module β Non-Recycle |
| Compatible Systems |
E100 and E110 Flame-Monitor Controls |
| Purge Time |
30 Seconds |
| Pilot/Main Trial for Ignition (PTFI/MTFI) |
10 Seconds |
| Flame Failure Response Time (FFRT) |
4 Seconds |
| Operation Type |
Non-Recycle |
| Communications |
RJ45 for Display, RJ12 for Modbus |
| Replaces |
Power Flame 398100 |
| Mounting |
Plug-in module |
| Temperature Range |
-40Β°F to +140Β°F |
β οΈ Common Symptoms of a Faulty Programmer Module
-
β Burner fails to start or complete purge cycle
-
β οΈ Lockout occurs immediately after trial for ignition
-
π₯ No flame detection despite proper ignition spark
-
βοΈ Inconsistent flame supervision or safety circuit resets
-
π§― Burner shuts down prematurely without error indication
β Frequently Asked Questions (FAQ)
Q1: What systems are compatible with the EP160?
A: The EP160 is designed for use with Fireye E100 and E110 Flame-Monitor controls.
Q2: What makes the EP160 βnon-recycleβ?
A: In the event of a flame failure, the EP160 locks out permanently until manually reset β ensuring safety.
Q3: Can this module replace Power Flame 398100?
A: β
Yes, the EP160 is a direct equivalent replacement for Power Flame 398100.
Q4: Does this module store operating history?
A: Yes β it records burner cycles, operating hours, and lockout events for diagnostic review.
Q5: Is it field-configurable?
A: The EP160 includes selectable settings for purge timing and interlock verification, depending on system design.
π Shopping Tips
-
β
Always confirm compatibility with your Fireye Flame-Monitor base (E100/E110).
-
βοΈ Check your existing moduleβs timing and recycle type (non-recycle vs recycle) before ordering.
-
π§ Replace modules showing erratic purge or lockout behavior.
-