- Two Way Valve
- 3" Connection Size
- Max. Safe Operating Pressure: 250 psi at 100 F water
- 100 Cv
- Chilled or hot water with up to 50% Glycol
- Temperature Fluid Rating 40 to 337 F
- Threaded
Features
• Direct or reverse acting
• Stainless steel stem with removable Teflon disc
• Self-adjusting, spring-loaded packing material to suit application
• Bronze, brass, or stainless steel plugs provide equal percentage or linear flow characteristics
• Suitable for pneumatic or electric/electronic actuation
• Repacking kits available for field servicing
V5011 Series Single-Seated, Two-Way, Straight-Through Valves (“Valves”) provide proportional control of steam and hot or chilled water in HVAC systems requiring tight shutoff.
V5011F1113