REPLACES
■ ASCO: 420347Y, 420600D
■ Eaton: SP1-600Y, SP1-600D, SP2-600Y
■ ERICO (Critec): TDX50C347/600
■ Intermatic: AG6503, L5F13Y3DG1
■ Siemens: TPS3L, TPS3G
■ Square D: SDSA3650, SDSA3650D
FEATURES
√ Maximum Surge Current Capacity: 150 kA
√ Delta or Wye configuration
√ NEMA Type 4X watertight plastic enclosure for outdoor and indoor installation
√ Green LED indicates surge protection present
√ Easily connects to electrical panel or disconnect for indoor and outdoor applications
√ UL Listed Type 1 or Type 2 SPD
SPECIFICATIONS
■ Service voltage (3-phase): 600 VAC Delta or 347/600 VAC Wye
■ Short Circuit Current Rating (SCCR): 200 kA
■ Nominal discharge current (In): 20kA
■ Protection mode:
• 3 for Delta configuration
• 6 for Wye configuration (neutral tied to ground)
■ Maximum Continuous Operation Voltage (MCOV):
• L-L: 920 VAC
• L-N: (for Wye configuration only): 460 VAC
■ VPR:
• Delta L-L: 2500 VAC
• Wye L-L: 2500 VAC
• Wye L-N: 1500 VAC
■ SPD type: Type 1 (can also be used in Type 2 applications)
■ Surge protection technology: TFMOV
■ Input power frequency: 50/60 Hz
■ Maximum surge current: 150 kA