AQUASTAT. BREAK ON RISE. MANUAL RESET. 130-270F. 250F STOP.

Manufacturer: Resideo
- Maximum Temperature Range 150 F - Includes Stop factory-set at 250 F (121 C) - Mounting Horizontal or Vertical - Operating Temperature Range 130 F to 270 F - Bulb Size (in.) 3/8 in. x 2 7/8 in. copper - Differential Temperature Manual Reset - Capillary Length (in.)1 1/2 in - Well Spud Size (in.)1/2 in - Switch Action: Contacts Break on Temp Rise; SPST Electrical Ratings: Millivolt--0.25 A @ 0.25 to 12 Vdc; At Full Load-- 8A @ 120 Vac: 1.3A @ 240 Vac; At Locked Rotor-- 48A @ 120 Vac: 30.6A @ 240 Vac Features - Totally enclosed Micro Switch snap-acting switches operate on temperature rise to setpoint. - Visible control point scale and external adjustment screw permit easy setting. - Horizontal or vertical insertion of the sensing element. - Direct or well immersion of the sensing element. - Models available for strap-on mounting. - Remote bulb model may be used to sense air temperature in ducts and in outside air sensing applications. - Select models include heat-conductive compound. - Select models have wells. - UL limit rated device. Aquastat Controllers are immersion type devices for limiting or regulating the temperature of liquids in boilers, storage tanks, and other applications where temperature control is required. L4006 are used in applications that utilize the existing wells.
SKU: RESIDEO:L4006E1000
Product Availability: 8
$131.74
This product must be purchased in increments of 1
i h

- Maximum Temperature Range 150 F
- Includes Stop factory-set at 250 F (121 C)
- Mounting Horizontal or Vertical
- Operating Temperature Range 130 F to 270 F
- Bulb Size (in.) 3/8 in. x 2 7/8 in. copper
- Differential Temperature Manual Reset
- Capillary Length (in.)1 1/2 in
- Well Spud Size (in.)1/2 in
- Switch Action: Contacts Break on Temp Rise; SPST

Electrical Ratings: Millivolt--0.25 A @ 0.25 to 12 Vdc; At Full Load-- 8A @ 120 Vac: 1.3A @ 240 Vac; At Locked Rotor-- 48A @ 120 Vac: 30.6A @ 240 Vac

Features
- Totally enclosed Micro Switch snap-acting switches operate on temperature rise to setpoint.
- Visible control point scale and external adjustment screw permit easy setting.
- Horizontal or vertical insertion of the sensing element.
- Direct or well immersion of the sensing element.
- Models available for strap-on mounting.
- Remote bulb model may be used to sense air temperature in ducts and in outside air sensing applications.
- Select models include heat-conductive compound.
- Select models have wells.
- UL limit rated device.

Aquastat Controllers are immersion type devices for limiting or regulating the temperature of liquids in boilers, storage tanks, and other applications where temperature control is required. L4006 are used in applications that utilize the existing wells.