DUAL AQUASTAT LESS WELL RANGE 140-240F. ADJ STOP AT HI LIMIT

Manufacturer: Resideo
- 120V - 60Hz - Maximum Safe Operating Pressure (psi)Immersion Well: 255 PSI - Maximum Safe Operating Pressure (kPa)Immersion Well: 1757 kPa - Temperature Range Maximum--150 F with 1.2 A 24 V load; 77 F with 1.4 A 24 V load - Mounting Horizontal - Electrical Connections Quick-Connect / Screw - Operating Humidity Range (% RH)0 to 95% RH, non-condensing - Operating Temperature Range High Limit-- 140 F to 240 F - Differential Temperature 8 F fixed - Switching Action SPST: High Limit & Circulator - Anticipator Setting 0.2 A - Capillary Length (in.)4 1/2 in - Insulation Depth (in.)1 1/2 in. to 3 in. less well Electrical Ratings, Burner At Full Load-- Low Voltage: 0.8 A max. @ 24 Vac: Line Voltage: 7.4 A @ 120 Vac: 3.7 A @ 240 Vac; At Locked Rotor-- Line Voltage: 44.4 A @ 120 Vac: 22.7 A @ 240 Vac Electrical Ratings, Circulator At Full Load-- 7.4 A @ 120 Vac: 3.7 A @ 240 Vac; At Locked Rotor-- 44.4 A @ 120 Vac: 22.2 A @ 240 Vac Features - High limit opens burner circuit only. - Include transformer and accessory terminals for adding a remote low limit controller. - Case available for horizontal or vertical mounting. - Requires a 24 Vac thermostat with heat anticipator set at 0.2A. -Tube of Heat Conductive Compound Included. Immersion-type controllers that combine high limit protection with switching relay control of burner and circulator motors.
SKU: RESIDEO:L8148A1017
Product Availability: 2
$290.61
This product must be purchased in increments of 1
i h

- 120V
- 60Hz
- Maximum Safe Operating Pressure (psi)Immersion Well: 255 PSI
- Maximum Safe Operating Pressure (kPa)Immersion Well: 1757 kPa
- Temperature Range Maximum--150 F with 1.2 A 24 V load; 77 F with 1.4 A 24 V load
- Mounting Horizontal
- Electrical Connections Quick-Connect / Screw
- Operating Humidity Range (% RH)0 to 95% RH, non-condensing
- Operating Temperature Range High Limit-- 140 F to 240 F
- Differential Temperature 8 F fixed
- Switching Action SPST: High Limit & Circulator
- Anticipator Setting 0.2 A
- Capillary Length (in.)4 1/2 in
- Insulation Depth (in.)1 1/2 in. to 3 in. less well

Electrical Ratings, Burner At Full Load-- Low Voltage: 0.8 A max. @ 24 Vac: Line Voltage: 7.4 A @ 120 Vac: 3.7 A @ 240 Vac; At Locked Rotor-- Line Voltage: 44.4 A @ 120 Vac: 22.7 A @ 240 Vac

Electrical Ratings, Circulator At Full Load-- 7.4 A @ 120 Vac: 3.7 A @ 240 Vac; At Locked Rotor-- 44.4 A @ 120 Vac: 22.2 A @ 240 Vac

Features
- High limit opens burner circuit only.
- Include transformer and accessory terminals for adding a remote low limit controller.
- Case available for horizontal or vertical mounting.
- Requires a 24 Vac thermostat with heat anticipator set at 0.2A.
-Tube of Heat Conductive Compound Included.

Immersion-type controllers that combine high limit protection with switching relay control of burner and circulator motors.

Products specifications
Manufacturer Resideo