S89F1098 DIRECT SPARK IGNIITON MODULE. 4 SECOND LOCKOUT. 30 SECOND
S89F1098
Direct Spark Ignition
Provide electronic control of direct spark ignition systems, with external spark transformers, used on gas-fired furnaces, boilers, conversion burners and other heating appliances.
Features
- Controls ignition sequence and gas control operation in direct spark ignition systems.
- Control separate 120 Vac spark generator that provides high voltage potential for main burner ignition.
- Lockout after one trial for ignition if main burner fails to ignite.
- Reset from thermostat after lockout. Use separate electrodes for spark ignition and flame sensing.
- Use any 24 Vac combination gas control designed for direct spark applications and rated at 2.0A or less.
- Electrical Ratings: 24 Vac
- Frequency: 60 Hz
- Max Ambient Temperature: -40 F to +175 F
- Flame Failure Re-ignition Time: 0.8 sec.
- Maximum Valve Load @ 24 Vac (Amps): 2A
- Ignition Trial Time: 4 Seconds
- Flame Sense: Two Rod
- Lockout Timing 4 Seconds
- Pre-Purge Time 30 Seconds.