The 007-IFC is designed to simplify piping, reduce installation costs and improve system performance when zoning with "00®" circulators. By locating the IFC inside the pump, a separate in-line flow check is eliminated. The low pressure drop of the IFC increases flow performance vs. in-line flow checks. Both the IFC and the cartridge are easily accessed for service.
• Hydronic Heating/Cooling
• Hydro-Air Fan Coils
• Radiant
• Indirect Water Heaters
Features
• Integral Flow Check (IFC®)
Simplifies piping
Prevents gravity flow/reverse flow
Eliminates separate in-line flow check
Reduces installed cost
Improves system performance
Easy to service
• Unique replaceable cartridge-Field serviceable
• Unmatched reliability-Maintenance free
• Quiet, efficient operation
• Self lubricating, No mechanical seal
• Wide range of applications
• Cast Iron construction, Flanged connections
Materials of Construction
Casing (Volute): Cast Iron
Integral Flow Check (IFC®):
Body, Plunger....Acetal
O-ring Seals......EPDM
Spring.............Stainless Steel
Stator Housing: Steel
Cartridge: Stainless Steel
Impeller: Non-Metallic
Shaft: Ceramic
Bearings: Carbon
O-Ring & Gaskets: EPDM
Performance Data
Flow Range: 0 - 12.5 GPM
Head Range: 0 - 11 Feet
Maximum Fluid Temperature: 240°F (115°C)
Maximum Working Pressure: 125 psi
Connection Sizes: 3/4”, 1”, 1-1/4” or 1-1/2” Flanged
Electrical Data
Volts: 115
Hz: 60
Ph: 1
Amps: .71
RPM: 3250
HP: 1/25
007F5IFCREPLACES: 007-F5-1 IFC