TEKMAR 132 - The Pump Sequencer 132 is designed to provide pump control for either stand-by or 2-stage operation. In stand-by mode, the 132 automatically switches over from the lead pump to the stand-by pump during a pump failure. In 2-stage mode, the 132 turns on the second stage pump to meet additional flow requirements
Dimensions 6-5/8" H x 7-9/16" W x 2-13/16" D (170 x 193 x 72 mm)
Approvals CSA C US, meets ICES & FCC regulations for EMI/RFI
Ambient Conditions Indoor use only, 32 to 120°F (0 to 50°C),
< 90% RH non-condensing
Power Supply 120 V +/- 10% 50/60 Hz 6 VA
Pump Relays 240 V (ac) 10 A 1/2 hp, pilot duty 3 A 720 VA
Alarm Relays 240 V (ac) 10 A 1/3 hp, pilot duty 2 A 240 VA
Demands 20 to 260 V (ac) 2 VA
Sensors NTC thermistor, 10 k? @ 77°F (25°C +/- 0.2°C) ß=3892
Optional Outdoor Sensor 070